EPA requirements according to DIN EN 61340-5-1
Work in accordance with standards

EPA requirements according to DIN EN 61340-5-1

ESD control
element
Product qualification a
Compliance verification b
Test procedure
Limits c
Based on testing procedures
Limits c
Work surfaces,
storage shelves
and transport
trolleys g
IEC 61340-2-3
Rgp < 1 x 109
Rp-p < 1 x 109
IEC 61340-2-3
Rg < 1 x 109
Wrist strap
connection point
-
-
-
Rg < 5 x 106
Flooring
IEC 61340-4-1 d,e
Rgp < 1 x 109
IEC 61340-4-1
Rg < 5 x 109
Ionization
IEC 61340-4-7
Decay (1000 V to 100 V
and
-1000 V to -100 V) < 20 s
Offset voltage < +/- 35 V
IEC 61340-4-7
Decay (1000 V to 100 V
and
-1000 V to -100 V) < 20 s
Offset voltage < +/- 35 V
Seating
IEC 61340-2-3 (measurement of resistance
to groundable point)
Rgp < 1 x 109
IEC 61340-4-9
Rg < 1 x 1011
EPA-clothing
IEC 61340-4-9
Rp-p < 1 x 1011
IEC 61340-4-9
Rp-p < 1 x 1011
Groundable
EPA clothing
IEC 61340-4-9
Rgp < 1 x 109
IEC 61340-4-9
Rgp < 1 x 109

Legend to the table

a
For product qualification, the environmental conditions for the test should be (12 ± 3) % relative humidity and (23 ± 2) °C. Unless specified in the referenced IEC standards, the minimum ambient temperature conditioning time for product qualification should be 48 h.
b
The test methods in the compliance verification column refer only to the basic test method. The test methods are not expected to be fully followed
c
Symbols used in this table: Rp-p refers to point-to-point resistance, Rg corresponds to resistance to ground and Rgp refers to resistance to groundable point.
d
The maximum admissible test voltage for the measurement of ESD floor coverings to be used for an ESD program that complies with this standard is 100 V.
e
If a flooring is used to ground the personnel handling ESDS, reference is made to the system requirements in table 2.
f
In situations where damage from the Charged Device Model (CDM) must be considered, a lower threshold of the point-to-point resistance Rp-p of 1 x 104 Ω is recommended.
g
Working surfaces are defined as any surface on which an ESD-sensitive element is placed.

Latest posts in the category "Knowledge"

blog/kachel_anforderungen_personenerdung_260x125px.png

Requirements for personal grounding according to DIN EN 61340-5-1

Personal grounding plays a crucial role in minimizing electrostatic discharges from people in electrostatically protected areas (EPAs).Here are the main requirements related to personal grounding according to this standard.

blog/kachel_esd_checkliste_260x125px.png

Checklist ESD Protective Measures

Protection against electrostatic discharge (ESD) is critical in industrial sectors such as electronics, semiconductor manufacturing, and others where sensitive electronic components are processed.
We offer you an overview with our checklist and essential questions.

blog/kachel_ergonomischer_Arbeitsplatz_260x125px.png

Ergonomic Workplace – Comfortable Working

Ergonomic working in the workplace is essential for the efficiency, safety and health of your employees. Therefore, protective measures and ergonomic principles must be observed in order to optimize the working environment and minimize health risks.

Latest posts from our blog

blog/kachel_bimos_neon_260x125px.png

NEONgenial from bimos – The NEON ESD work swivel chair

Ergonomic, modular and perfect for ESD-protected working environments: The bimos NEON task swivel chairs combine functionality and design. With individual adaptability and optimum comfort, they offer an ideal solution for modern workstations in sensitive areas.

blog/Kachel_GetRacing_260x125px.jpg

GET racing: Together for innovation in racing

As a proud sponsor, we are providing the dedicated Formula Student team with an ESD-compliant complete cabinet for component storage. Find out how this collaboration brings high-tech and passion together.

home/tiles/kachel_kununu_260x125px.png

kununu Top Company 2025 – for the third time in a row!

We are delighted to once again carry the kununu Top Company seal in 2025! As one of the most popular 5 % of companies on kununu, this award shows us that our employees value our corporate culture and working conditions.